Customization: | Available |
---|---|
Certification: | ISO9001 |
Shell Material: | Steel Plate |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Project
|
Company
|
Load switch cabinet
|
Combination cabinet
|
Circuit breaker cabinet
|
Rated voltage
|
kV
|
12
|
12
|
12
|
Rated frequency
|
Hz
|
50/60
|
50/60
|
50/60
|
Rated current
|
A
|
|
|
|
Main busbar
|
A
|
630
|
630
|
630
|
Branch bus
|
A
|
630
|
125(depending on the rated current of the melter)
|
630
|
Rated insulation level
|
kV
|
|
|
|
Power Frequency Voltage Withstand
(Interphase and Relative)
|
kV
|
42
|
42
|
42
|
Power Frequency Voltage Withstand
(Fracture Intersection)
|
kV
|
48
|
48
|
48
|
Power Frequency Voltage Withstand
(Control and Auxiliary Circuit)
|
kV
|
2
|
2
|
2
|
Residual Impulse Volyage
(Interphase and Relative)
|
kV
|
75
|
75
|
75
|
Lightning Impulse Voltage Resistance
(Fracture Intersetion)
|
kV
|
85
|
85
|
85
|
Main circuit
|
kA
|
20/3s
|
-
|
25/2s
|
Grounding circuit
|
kA
|
20/3s
|
-
|
25/2s
|
Rated peak current
|
kA
|
50
|
-
|
63
|
Rated short circuit switching current(peak)
|
kA
|
50
|
80
|
63
|
Rated short circuit breaking current
|
kA
|
-
|
31.5
|
25
|
Rated transfer current
|
A
|
-
|
1700
|
-
|
Rated Active load breaking current
|
A
|
630
|
-
|
-
|
Rated closed-loop switching-off current
|
A
|
630
|
-
|
630
|
Rated Cable Charhing Open- Out Current
|
A
|
10
|
-
|
15
|
Protection level
|
|
IP3X
|
IP3X
|
IP3X
|